Numerical - Effect of increasing Power Factor

Q.  If an alternator is supplying load of 350 kW at 0.6 pf lagging and its power factor is raised to unity then to supply the alternator for the same kVA loading, the extra required kilowatts will be
- Published on 06 Oct 15

a. 205 kW
b. 212 kW
c. 233 kW
d. 246 kW

ANSWER: 233 kW