Slip Test and Reluctance Power of Alternators - - MCQs with answers
Q1. Depending upon the reluctances offered along the direct axis and quadrature axis, the armature reaction flux willa. Lead the armature current
b. Lags behind the armature current
c. In phase with the armature current
d. Either (b) or (c)
View Answer / Hide AnswerANSWER: b. Lags behind the armature current
Q2. The method used to determine Xd and Xq, the direct and quadrature axis reactance is calleda. Reactance test
b. Blondel’s two reaction theory
c. Slip test
d. All of the above
View Answer / Hide AnswerQ3. In a salient pole synchronous generator if Ea is the internal induced emf with Id and Iq be the direct axis and quadrature axis component of armature current, thena. I
q is in phase with E
ab. I
d is in phase with E
ac. I
d is at 90 degree to E
ad. Both (a) & (c)
View Answer / Hide AnswerANSWER: d. Both (a) & (c)
Q4. The direct axis reactance (Xd) and quadrature axis reactance (Xq) obtained from slip test area. X
d = minimum voltage/minimum current , X
q = maximum voltage/maximum current
b. X
d = minimum voltage/maximum current , X
q = maximum voltage/maximum current
c. X
d = maximum voltage/minimum current , X
q = minimum voltage/maximum current
d. X
d = maximum voltage/maximum current , X
q = minimum voltage/minimum current
View Answer / Hide AnswerANSWER: c. Xd = maximum voltage/minimum current , Xq = minimum voltage/maximum current
Q5. In a salient pole synchronous generator direct axis reactance isa. Greater than quadrature axis reactance
b. Less than quadrature axis reactance
c. Equal to quadrature axis reactance
d. None of the above
View Answer / Hide AnswerANSWER: a. Greater than quadrature axis reactance
Q6. A synchronous generator has a direct axis and quadrature axis reactances of 0.6 per unit and 0.3 per unit respectively. What will be its total induced emf on open circuit if it is used to supply full load at rated voltage at 0.8 power factor ( Assume rated terminal voltage is equal to 1 pu, full load armature current be 1 pu and armature resistance to be 0).a. 1.099 pu
b. 1.199 pu
c. 1.488 pu
d. 1.588 pu
View Answer / Hide AnswerQ7. A 3 phase star connected synchronous generator having direct axis reactance of 8 ohm and quadrature axis reactance of 6 ohm supplies current of 9 A with phase angle of 20 degree lagging at 415 V. Then its direct axis component of armature current and quadrature axis component of armature current area. 8.04 A, 4.04 A
b. 4.04 A, 6.84 A
c. 6.84 A, 8.04 A
d. 4.04 A, 8.04 A
View Answer / Hide AnswerANSWER: d. 4.04 A, 8.04 A
Q8. The reluctance power of a salient pole alternator is given bya. V
2[X
d - X
q / 2X
dX
q] sin2 δ
b. V
2[X
q - X
d / 2X
d X
q]sin2 δ
c. V
2[X
d - X
q / X
dX
q]sin δ
d. V[X
d - X
q / 2X
d X
q]sin2 δ
View Answer / Hide AnswerANSWER: a. V2[Xd - Xq / 2XdXq] sin2 δ
Q9. In case of salient pole alternators, maximum output power can be obtained when power angle (d) isa. Less than 90 degree
b. Equal to 90 degree
c. Greater than 90 degree
d. None of the above
View Answer / Hide AnswerANSWER: a. Less than 90 degree